Product code: BE-280BD5-B01 C

Heat rejection i
150.13 kW
Air flow
41,195 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 41,195 m³/h
External surface 547.5 m²
Inner volume 77.4 dm³
Fin materialAluminium
Net weight 596 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-280BD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
150.128 kW Fluid flow 26.05 m³/h Pressure drop 74.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
116.208 kW Fluid flow 20.15 m³/h Pressure drop 47.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 89.63 not rated not rated not rated not rated not rated
40 150.13 89.62 not rated not rated not rated not rated
45 209.05 149.65 89.62 not rated not rated not rated
50 267.49 208.14 149.21 89.63 not rated not rated
55 325.68 266.15 207.35 148.90 89.70 not rated
60 383.74 323.94 265.01 206.75 148.73 89.86

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 69.97 not rated not rated not rated not rated not rated
40 116.21 69.95 not rated not rated not rated not rated
45 161.16 115.80 69.95 not rated not rated not rated
50 205.68 160.41 115.46 69.94 not rated not rated
55 250.01 204.60 159.77 115.21 70.00 not rated
60 294.22 248.61 203.69 159.29 115.09 70.14

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 150.128 26.05 74.2
Low speed (Y) 116.208 20.15 47.1

Dimensions

Dimension drawing of BE-280BD5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 2660 mm
F 1050 mm
G 3260 mm
E1 1130 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3260 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.