BE-2x191CB5-B04T C
197.89 kW
Defrost: None
Product code: BE-280CD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 44,712 m³/h |
|---|---|
| External surface | 1,590.3 m² |
| Inner volume | 204.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,033 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-280CD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 123.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 197.91 | 122.44 | not rated | not rated | not rated | not rated |
| 45 | 270.63 | 196.35 | 121.81 | not rated | not rated | not rated |
| 50 | 342.69 | 268.29 | 194.99 | 121.28 | not rated | not rated |
| 55 | 414.46 | 339.59 | 266.24 | 193.85 | 120.90 | not rated |
| 60 | 486.07 | 410.61 | 336.88 | 264.53 | 192.99 | 120.72 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 94.94 | not rated | not rated | not rated | not rated | not rated |
| 40 | 151.15 | 94.34 | not rated | not rated | not rated | not rated |
| 45 | 205.78 | 149.87 | 93.80 | not rated | not rated | not rated |
| 50 | 259.93 | 203.89 | 148.74 | 93.35 | not rated | not rated |
| 55 | 313.85 | 257.43 | 202.23 | 147.81 | 93.03 | not rated |
| 60 | 367.66 | 310.77 | 255.25 | 200.85 | 147.11 | 92.86 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 197.906 | 34.33 | 97.7 |
| Low speed (Y) | 151.146 | 26.22 | 60.5 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 5260 mm |
| F | 1050 mm |
| G | 5860 mm |
| E1 | 2430 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 5860 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.