Skip to Content

Dry cooler BE-291AB5-B04 C

Dry cooler BE-291AB5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-291AB5-B04 C

Heat rejection i
156.54 kW
Air flow
56,832 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 56,832 m³/h
External surface 477.6 m²
Inner volume 73.2 dm³
Fin materialAluminium
Net weight 590 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
BE-291AB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
156.535 kW Fluid flow 27.17 m³/h Pressure drop 78.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
128.131 kW Fluid flow 22.24 m³/h Pressure drop 54.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 90.46 not rated not rated not rated not rated not rated
40 156.54 90.72 not rated not rated not rated not rated
45 221.27 156.40 90.93 not rated not rated not rated
50 285.58 220.78 156.28 91.13 not rated not rated
55 349.68 284.73 220.35 156.21 91.35 not rated
60 413.69 348.51 284.01 220.03 156.22 91.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 74.57 not rated not rated not rated not rated not rated
40 128.13 74.76 not rated not rated not rated not rated
45 180.49 127.96 74.91 not rated not rated not rated
50 232.46 180.00 127.82 75.06 not rated not rated
55 284.24 231.66 179.58 127.72 75.22 not rated
60 335.93 283.15 230.97 179.26 127.71 75.43

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 156.535 27.17 78.0
Low speed (Y) 128.131 22.24 54.7

Dimensions

Dimension drawing of BE-291AB5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 2860 mm
F 1050 mm
G 3460 mm
E1 1230 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3460 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.