Skip to Content

Dry cooler BE-2X280AC5-B01T C

Dry cooler BE-2X280AC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2X280AC5-B01T C

Heat rejection i
286.58 kW
Air flow
83,598 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 83,598 m³/h
External surface 1,133.0 m²
Inner volume 175.8 dm³
Fin materialAluminium
Net weight 1,431 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2X280AC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
286.577 kW Fluid flow 49.74 m³/h Pressure drop 55.0 kPa
Heat rejection · Low speed (Y)
225.812 kW Fluid flow 39.16 m³/h Pressure drop 36.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 168.43 not rated not rated not rated not rated not rated
40 286.58 168.68 not rated not rated not rated not rated
45 401.76 285.91 168.88 not rated not rated not rated
50 515.93 400.27 285.34 169.09 not rated not rated
55 629.69 513.64 398.95 284.92 169.39 not rated
60 743.18 626.63 511.69 397.97 284.74 169.79

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 133.98 not rated not rated not rated not rated not rated
40 225.81 134.13 not rated not rated not rated not rated
45 315.12 225.20 134.27 not rated not rated not rated
50 403.58 313.82 224.68 134.39 not rated not rated
55 491.64 401.63 312.72 224.26 134.57 not rated
60 579.48 489.06 399.98 311.83 224.04 134.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 286.577 49.74 55.0
Low speed (Y) 225.812 39.16 36.0

Dimensions

Dimension drawing of BE-2X280AC5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 2850 mm
F 2330 mm
G 3450 mm
E1 1250 mm
H 3100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3450 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.