Skip to Content

Dry cooler BE-2X280BC1-B01T C

Dry cooler BE-2X280BC1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2X280BC1-B01T C

Heat rejection i
279.59 kW
Air flow
82,096 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 82,096 m³/h
External surface 947.4 m²
Inner volume 132.1 dm³
Fin materialAluminium
Net weight 1,338 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2X280BC1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
279.590 kW Fluid flow 48.53 m³/h Pressure drop 41.7 kPa
Heat rejection · Low speed (Y)
217.989 kW Fluid flow 37.84 m³/h Pressure drop 26.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 162.81 not rated not rated not rated not rated not rated
40 279.59 163.37 not rated not rated not rated not rated
45 393.10 279.17 163.85 not rated not rated not rated
50 505.55 391.85 278.81 164.29 not rated not rated
55 617.50 503.51 390.81 278.61 164.76 not rated
60 729.21 614.74 501.80 389.99 278.60 165.35

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 127.95 not rated not rated not rated not rated not rated
40 217.99 128.40 not rated not rated not rated not rated
45 305.14 217.57 128.77 not rated not rated not rated
50 391.40 304.08 217.25 129.13 not rated not rated
55 477.25 389.73 303.21 217.07 129.52 not rated
60 562.87 474.98 388.34 302.59 217.09 130.02

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 279.590 48.53 41.7
Low speed (Y) 217.989 37.84 26.7

Dimensions

Dimension drawing of BE-2X280BC1-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 2650 mm
F 2330 mm
G 3250 mm
E1 1150 mm
H 2900 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3250 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.