BE-2x291CB1-C04C C
397.03 kW
Defrost: None
Product code: BE-2X380BC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 124,613 m³/h |
|---|---|
| External surface | 1,203.8 m² |
| Inner volume | 191.9 dm³ |
| Fin material | Aluminium |
| Net weight | 1,801 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2X380BC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 233.82 | not rated | not rated | not rated | not rated | not rated |
| 40 | 396.73 | 234.05 | not rated | not rated | not rated | not rated |
| 45 | 555.94 | 395.90 | 234.27 | not rated | not rated | not rated |
| 50 | 713.97 | 554.15 | 395.19 | 234.49 | not rated | not rated |
| 55 | 871.44 | 711.24 | 552.62 | 394.70 | 234.81 | not rated |
| 60 | 1028.60 | 867.80 | 708.92 | 551.48 | 394.52 | 235.30 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 185.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 312.72 | 185.83 | not rated | not rated | not rated | not rated |
| 45 | 436.61 | 311.99 | 185.98 | not rated | not rated | not rated |
| 50 | 559.45 | 435.09 | 311.37 | 186.16 | not rated | not rated |
| 55 | 681.85 | 557.15 | 433.76 | 310.96 | 186.43 | not rated |
| 60 | 803.98 | 678.81 | 555.23 | 432.83 | 310.83 | 186.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 396.729 | 68.86 | 100.2 |
| Low speed (Y) | 312.718 | 54.27 | 65.8 |
| A | 2778 mm |
|---|---|
| B | 2400 mm |
| C | 3750 mm |
| F | 2330 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2400 mm |
| Height | 2778 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.