BE-t-280GB1-B01 C
153.74 kW
Defrost: None
Product code: BE-2x180CB5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 44,796 m³/h |
|---|---|
| External surface | 730.7 m² |
| Inner volume | 108.4 dm³ |
| Fin material | Aluminium |
| Net weight | 959 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.1 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x180CB5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 91.27 | not rated | not rated | not rated | not rated | not rated |
| 40 | 153.59 | 91.18 | not rated | not rated | not rated | not rated |
| 45 | 214.45 | 152.99 | 91.08 | not rated | not rated | not rated |
| 50 | 274.82 | 213.37 | 152.46 | 91.02 | not rated | not rated |
| 55 | 334.96 | 273.28 | 212.43 | 152.01 | 90.99 | not rated |
| 60 | 395.00 | 332.98 | 271.93 | 211.62 | 151.71 | 91.04 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 73.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 122.04 | 73.00 | not rated | not rated | not rated | not rated |
| 45 | 169.71 | 121.46 | 72.88 | not rated | not rated | not rated |
| 50 | 216.98 | 168.74 | 120.97 | 72.79 | not rated | not rated |
| 55 | 264.07 | 215.63 | 167.89 | 120.56 | 72.75 | not rated |
| 60 | 311.05 | 262.33 | 214.43 | 167.19 | 120.27 | 72.77 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 153.589 | 26.66 | 82.5 |
| Low speed (Y) | 122.039 | 21.18 | 54.9 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 2850 mm |
| F | 2230 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.