BE-291BD1-B04 C
198.84 kW
Defrost: None
Product code: BE-2x180CD1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 44,200 m³/h |
|---|---|
| External surface | 1,675.8 m² |
| Inner volume | 194.0 dm³ |
| Fin material | Aluminium |
| Net weight | 1,296 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x180CD1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 124.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 200.21 | 124.22 | not rated | not rated | not rated | not rated |
| 45 | 273.31 | 198.62 | 123.59 | not rated | not rated | not rated |
| 50 | 345.71 | 270.89 | 197.21 | 123.07 | not rated | not rated |
| 55 | 417.78 | 342.50 | 268.78 | 196.05 | 122.72 | not rated |
| 60 | 489.69 | 413.80 | 339.69 | 267.02 | 195.18 | 122.55 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 151.80 | 95.06 | not rated | not rated | not rated | not rated |
| 45 | 206.29 | 150.50 | 94.53 | not rated | not rated | not rated |
| 50 | 260.25 | 204.36 | 149.37 | 94.09 | not rated | not rated |
| 55 | 313.99 | 257.72 | 202.67 | 148.43 | 93.79 | not rated |
| 60 | 367.61 | 310.86 | 255.51 | 201.29 | 147.74 | 93.65 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 200.214 | 34.73 | 81.5 |
| Low speed (Y) | 151.801 | 26.33 | 49.8 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 2850 mm |
| F | 2330 mm |
| G | 3450 mm |
| E1 | 2450 mm |
| H | 3100 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3450 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.