Skip to Content

Dry cooler BE-2x180DB1-B01C C

Dry cooler BE-2x180DB1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x180DB1-B01C C

Heat rejection i
139.39 kW
Air flow
43,836 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 43,836 m³/h
External surface 490.7 m²
Inner volume 67.7 dm³
Fin materialAluminium
Net weight 820 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-2x180DB1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
139.386 kW Fluid flow 24.19 m³/h Pressure drop 64.6 kPa
Heat rejection · Low speed (Y)
110.590 kW Fluid flow 19.19 m³/h Pressure drop 42.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 81.53 not rated not rated not rated not rated not rated
40 139.39 81.66 not rated not rated not rated not rated
45 195.85 139.06 81.75 not rated not rated not rated
50 251.87 195.12 138.76 81.84 not rated not rated
55 307.67 250.75 194.47 138.53 81.95 not rated
60 363.37 306.19 249.77 193.96 138.40 82.11

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 65.14 not rated not rated not rated not rated not rated
40 110.59 65.21 not rated not rated not rated not rated
45 154.83 110.27 65.27 not rated not rated not rated
50 198.68 154.17 109.99 65.33 not rated not rated
55 242.36 197.69 153.58 109.77 65.40 not rated
60 285.93 241.05 196.83 153.12 109.64 65.52

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 139.386 24.19 64.6
Low speed (Y) 110.590 19.19 42.9

Dimensions

Dimension drawing of BE-2x180DB1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 2250 mm
F 2230 mm
G 2850 mm
E1 1850 mm
H 2500 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2850 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.