Skip to Content

Dry cooler BE-2x180DD1-B01T C

Dry cooler BE-2x180DD1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x180DD1-B01T C

Heat rejection i
180.50 kW
Air flow
43,285 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 43,285 m³/h
External surface 968.5 m²
Inner volume 115.8 dm³
Fin materialAluminium
Net weight 1,041 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-2x180DD1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
180.496 kW Fluid flow 31.30 m³/h Pressure drop 73.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
138.122 kW Fluid flow 23.96 m³/h Pressure drop 45.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 110.10 not rated not rated not rated not rated not rated
40 180.50 109.78 not rated not rated not rated not rated
45 248.85 179.43 109.49 not rated not rated not rated
50 316.53 247.12 178.50 109.26 not rated not rated
55 383.90 314.16 245.61 177.75 109.13 not rated
60 451.11 380.90 312.09 244.37 177.21 109.13

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 85.00 not rated not rated not rated not rated not rated
40 138.12 84.72 not rated not rated not rated not rated
45 189.59 137.24 84.46 not rated not rated not rated
50 240.53 188.18 136.47 84.26 not rated not rated
55 291.23 238.62 186.95 135.84 84.14 not rated
60 341.80 288.82 236.95 185.95 135.40 84.14

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 180.496 31.30 73.2
Low speed (Y) 138.122 23.96 45.5

Dimensions

Dimension drawing of BE-2x180DD1-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 2250 mm
F 2330 mm
G 2850 mm
E1 1850 mm
H 2500 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2850 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.