BE-2x180DC1-B01T C
168.23 kW
Defrost: None
Product code: BE-2x191DB1-C04C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 57,406 m³/h |
|---|---|
| External surface | 475.6 m² |
| Inner volume | 65.7 dm³ |
| Fin material | Aluminium |
| Net weight | 830 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-2x191DB1-C04C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 97.32 | not rated | not rated | not rated | not rated | not rated |
| 40 | 167.46 | 97.54 | not rated | not rated | not rated | not rated |
| 45 | 236.08 | 167.23 | 97.73 | not rated | not rated | not rated |
| 50 | 304.21 | 235.43 | 167.02 | 97.91 | not rated | not rated |
| 55 | 372.11 | 303.16 | 234.87 | 166.88 | 98.11 | not rated |
| 60 | 439.88 | 370.67 | 302.26 | 234.43 | 166.84 | 98.35 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 79.13 | not rated | not rated | not rated | not rated | not rated |
| 40 | 135.28 | 79.28 | not rated | not rated | not rated | not rated |
| 45 | 190.08 | 135.02 | 79.41 | not rated | not rated | not rated |
| 50 | 244.45 | 189.46 | 134.80 | 79.54 | not rated | not rated |
| 55 | 298.62 | 243.49 | 188.93 | 134.64 | 79.68 | not rated |
| 60 | 352.68 | 297.32 | 242.66 | 188.52 | 134.58 | 79.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 167.464 | 29.06 | 94.1 |
| Low speed (Y) | 135.280 | 23.48 | 64.4 |
| A | 2511 mm |
|---|---|
| B | 2300 mm |
| C | 2250 mm |
| F | 2230 mm |
| G | 2850 mm |
| E1 | 1850 mm |
| H | 2500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2250 mm |
|---|---|
| Width | 2300 mm |
| Height | 2511 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.