Skip to Content

Dry cooler BE-2x280BD5-B01T C

Dry cooler BE-2x280BD5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x280BD5-B01T C

Heat rejection i
290.22 kW
Air flow
80,970 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 80,970 m³/h
External surface 1,002.9 m²
Inner volume 154.2 dm³
Fin materialAluminium
Net weight 1,383 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x280BD5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
290.224 kW Fluid flow 50.37 m³/h Pressure drop 85.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
224.357 kW Fluid flow 38.91 m³/h Pressure drop 54.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 172.95 not rated not rated not rated not rated not rated
40 290.22 172.99 not rated not rated not rated not rated
45 404.51 289.38 173.02 not rated not rated not rated
50 517.87 402.88 288.68 173.10 not rated not rated
55 630.78 515.48 401.50 288.12 173.29 not rated
60 743.44 627.64 513.44 400.45 287.90 173.63

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 134.85 not rated not rated not rated not rated not rated
40 224.36 134.87 not rated not rated not rated not rated
45 311.41 223.65 134.88 not rated not rated not rated
50 397.66 310.08 223.08 134.96 not rated not rated
55 483.54 395.73 308.97 222.67 135.08 not rated
60 569.21 481.02 394.12 308.16 222.51 135.39

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 290.224 50.37 85.3
Low speed (Y) 224.357 38.91 54.0

Dimensions

Dimension drawing of BE-2x280BD5-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 2650 mm
F 2330 mm
G 3250 mm
E1 1150 mm
H 2900 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3250 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.