Skip to Content

Dry cooler BE-2x280CB1-B01T C

Dry cooler BE-2x280CB1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x280CB1-B01T C

Heat rejection i
344.39 kW
Air flow
89,975 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 89,975 m³/h
External surface 2,010.9 m²
Inner volume 245.1 dm³
Fin materialAluminium
Net weight 1,873 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.1 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x280CB1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
344.393 kW Fluid flow 59.73 m³/h Pressure drop 77.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
269.835 kW Fluid flow 46.80 m³/h Pressure drop 49.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 207.08 not rated not rated not rated not rated not rated
40 344.39 206.63 not rated not rated not rated not rated
45 478.15 342.61 206.19 not rated not rated not rated
50 610.74 475.17 341.04 205.84 not rated not rated
55 742.77 606.56 472.52 339.73 205.61 not rated
60 874.49 737.43 602.87 470.31 338.77 205.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 163.68 not rated not rated not rated not rated not rated
40 269.84 163.20 not rated not rated not rated not rated
45 373.00 268.25 162.76 not rated not rated not rated
50 475.18 370.40 266.84 162.41 not rated not rated
55 576.90 471.59 368.10 265.67 162.20 not rated
60 678.37 572.35 468.44 366.19 264.83 162.16

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 344.393 59.73 77.0
Low speed (Y) 269.835 46.80 49.9

Dimensions

Dimension drawing of BE-2x280CB1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 5250 mm
F 2330 mm
G 5850 mm
E1 2450 mm
H 5500 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5850 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.