BE-480FC1-B01 C
397.65 kW
Defrost: None
Product code: BE-2x280CD1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 88,400 m³/h |
|---|---|
| External surface | 3,351.5 m² |
| Inner volume | 395.5 dm³ |
| Fin material | Aluminium |
| Net weight | 2,260 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x280CD1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 246.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 398.02 | 245.53 | not rated | not rated | not rated | not rated |
| 45 | 544.55 | 395.00 | 244.50 | not rated | not rated | not rated |
| 50 | 689.54 | 539.86 | 392.34 | 243.66 | not rated | not rated |
| 55 | 833.83 | 683.25 | 535.75 | 390.14 | 243.08 | not rated |
| 60 | 977.74 | 825.98 | 677.74 | 532.34 | 388.52 | 242.87 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 189.08 | not rated | not rated | not rated | not rated | not rated |
| 40 | 302.03 | 188.10 | not rated | not rated | not rated | not rated |
| 45 | 411.28 | 299.56 | 187.21 | not rated | not rated | not rated |
| 50 | 519.38 | 407.53 | 297.40 | 186.49 | not rated | not rated |
| 55 | 626.96 | 514.39 | 404.24 | 295.61 | 185.99 | not rated |
| 60 | 734.26 | 620.77 | 510.04 | 401.53 | 294.31 | 185.80 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 398.018 | 69.04 | 42.3 |
| Low speed (Y) | 302.031 | 52.39 | 25.8 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 5250 mm |
| F | 2330 mm |
| G | 5850 mm |
| E1 | 2450 mm |
| H | 5500 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.