Skip to Content

Dry cooler BE-2x291AC5-C04C C

Dry cooler BE-2x291AC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x291AC5-C04C C

Heat rejection i
313.87 kW
Air flow
103,828 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 103,828 m³/h
External surface 933.6 m²
Inner volume 144.1 dm³
Fin materialAluminium
Net weight 1,293 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.5 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x291AC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
313.868 kW Fluid flow 54.47 m³/h Pressure drop 89.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
250.031 kW Fluid flow 43.39 m³/h Pressure drop 59.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 182.36 not rated not rated not rated not rated not rated
40 313.87 182.94 not rated not rated not rated not rated
45 442.51 313.68 183.44 not rated not rated not rated
50 570.22 441.64 313.57 183.93 not rated not rated
55 697.48 568.69 440.96 313.58 184.46 not rated
60 824.52 695.33 567.45 440.52 313.79 185.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 146.60 not rated not rated not rated not rated not rated
40 250.03 147.05 not rated not rated not rated not rated
45 350.95 249.85 147.44 not rated not rated not rated
50 451.02 350.20 249.74 147.85 not rated not rated
55 550.72 449.76 349.64 249.76 148.32 not rated
60 650.17 548.91 448.73 349.33 250.00 148.91

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 313.868 54.47 89.2
Low speed (Y) 250.031 43.39 59.5

Dimensions

Dimension drawing of BE-2x291AC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 2850 mm
F 2230 mm
G 3450 mm
E1 1250 mm
H 3100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2850 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.