Dry cooler BE-2x291BC5-B04T C

Dry cooler BE-2x291BC5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x291BC5-B04T C

Heat rejection i
324.92 kW
Air flow
109,588 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 109,588 m³/h
External surface 875.5 m²
Inner volume 140.3 dm³
Fin materialAluminium
Net weight 1,378 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-2x291BC5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
324.917 kW Fluid flow 56.39 m³/h Pressure drop 58.2 kPa
Heat rejection · Low speed (Y)
259.986 kW Fluid flow 45.12 m³/h Pressure drop 39.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 187.97 not rated not rated not rated not rated not rated
40 324.92 188.64 not rated not rated not rated not rated
45 458.66 324.66 189.21 not rated not rated not rated
50 591.39 457.60 324.45 189.75 not rated not rated
55 723.63 589.57 456.72 324.38 190.30 not rated
60 855.62 721.08 588.04 456.09 324.48 190.94

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 151.42 not rated not rated not rated not rated not rated
40 259.99 151.99 not rated not rated not rated not rated
45 365.70 259.78 152.47 not rated not rated not rated
50 470.50 364.86 259.60 152.92 not rated not rated
55 574.89 469.05 364.12 259.52 153.38 not rated
60 679.04 572.85 467.80 363.59 259.62 153.93

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 324.917 56.39 58.2
Low speed (Y) 259.986 45.12 39.1

Dimensions

Dimension drawing of BE-2x291BC5-B04T C
Dimension drawing
Dimensions as drawn
A 2910 mm
B 2400 mm
C 2850 mm
F 2330 mm
G 3450 mm
E1 1250 mm
H 3100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3450 mm
Width 2400 mm
Height 2910 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.