BE-480AD5-B01 C
328.29 kW
Defrost: None
Product code: BE-2x291DB5-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 117,973 m³/h |
|---|---|
| External surface | 984.9 m² |
| Inner volume | 152.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,521 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 96.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-2x291DB5-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 190.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 328.34 | 190.76 | not rated | not rated | not rated | not rated |
| 45 | 463.40 | 327.89 | 191.15 | not rated | not rated | not rated |
| 50 | 597.49 | 462.13 | 327.48 | 191.48 | not rated | not rated |
| 55 | 731.17 | 595.44 | 461.01 | 327.18 | 191.87 | not rated |
| 60 | 864.59 | 728.36 | 593.65 | 460.13 | 327.06 | 192.32 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 155.35 | not rated | not rated | not rated | not rated | not rated |
| 40 | 266.60 | 155.71 | not rated | not rated | not rated | not rated |
| 45 | 375.16 | 266.10 | 155.98 | not rated | not rated | not rated |
| 50 | 482.87 | 373.96 | 265.68 | 156.23 | not rated | not rated |
| 55 | 590.20 | 480.98 | 372.89 | 265.34 | 156.51 | not rated |
| 60 | 697.32 | 587.64 | 479.32 | 372.05 | 265.18 | 156.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 328.339 | 56.99 | 63.6 |
| Low speed (Y) | 266.595 | 46.27 | 43.8 |
| A | 2910 mm |
|---|---|
| B | 2400 mm |
| C | 4050 mm |
| F | 2330 mm |
| G | 4650 mm |
| E1 | 1850 mm |
| H | 4300 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2910 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.