BE-580AD5-B01 C
409.24 kW
Defrost: None
Product code: BE-2x380AB1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 127,521 m³/h |
|---|---|
| External surface | 1,508.2 m² |
| Inner volume | 208.2 dm³ |
| Fin material | Aluminium |
| Net weight | 1,874 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x380AB1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 238.56 | not rated | not rated | not rated | not rated | not rated |
| 40 | 408.80 | 238.99 | not rated | not rated | not rated | not rated |
| 45 | 575.09 | 407.98 | 239.33 | not rated | not rated | not rated |
| 50 | 740.09 | 573.14 | 407.26 | 239.69 | not rated | not rated |
| 55 | 904.48 | 737.05 | 571.45 | 406.74 | 240.10 | not rated |
| 60 | 1068.55 | 900.38 | 734.40 | 570.10 | 406.50 | 240.65 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 191.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 325.55 | 191.93 | not rated | not rated | not rated | not rated |
| 45 | 455.98 | 324.73 | 192.13 | not rated | not rated | not rated |
| 50 | 585.23 | 454.15 | 324.02 | 192.36 | not rated | not rated |
| 55 | 713.99 | 582.50 | 452.60 | 323.49 | 192.66 | not rated |
| 60 | 842.46 | 710.36 | 580.16 | 451.41 | 323.20 | 193.12 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 408.798 | 70.95 | 76.3 |
| Low speed (Y) | 325.549 | 56.50 | 50.9 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 4050 mm |
| F | 2330 mm |
| G | 4650 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| H | 4300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.