BE-t-2x380GC5-B01C C
435.03 kW
Defrost: None
Product code: BE-2x380BD5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 121,455 m³/h |
|---|---|
| External surface | 1,504.7 m² |
| Inner volume | 226.0 dm³ |
| Fin material | Aluminium |
| Net weight | 1,903 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x380BD5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 259.34 | not rated | not rated | not rated | not rated | not rated |
| 40 | 435.28 | 259.40 | not rated | not rated | not rated | not rated |
| 45 | 606.74 | 434.03 | 259.45 | not rated | not rated | not rated |
| 50 | 776.79 | 604.29 | 432.97 | 259.58 | not rated | not rated |
| 55 | 946.19 | 773.21 | 602.23 | 432.14 | 259.87 | not rated |
| 60 | 1115.19 | 941.47 | 770.16 | 600.66 | 431.81 | 260.39 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 202.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 336.49 | 202.24 | not rated | not rated | not rated | not rated |
| 45 | 467.09 | 335.44 | 202.27 | not rated | not rated | not rated |
| 50 | 596.49 | 465.10 | 334.58 | 202.38 | not rated | not rated |
| 55 | 725.31 | 593.59 | 463.44 | 333.98 | 202.58 | not rated |
| 60 | 853.83 | 721.54 | 591.17 | 462.22 | 333.74 | 203.04 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 435.281 | 75.54 | 82.7 |
| Low speed (Y) | 336.493 | 58.36 | 52.3 |
| A | 2778 mm |
|---|---|
| B | 2400 mm |
| C | 3750 mm |
| F | 2330 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2400 mm |
| Height | 2778 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.