BE-t-2x391GC1-C04C C
576.54 kW
Defrost: None
Product code: BE-2x380CD5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 133,196 m³/h |
|---|---|
| External surface | 4,249.6 m² |
| Inner volume | 602.3 dm³ |
| Fin material | Aluminium |
| Net weight | 3,083 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x380CD5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 355.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 576.64 | 353.49 | not rated | not rated | not rated | not rated |
| 45 | 791.81 | 572.62 | 352.10 | not rated | not rated | not rated |
| 50 | 1004.88 | 785.49 | 569.05 | 350.96 | not rated | not rated |
| 55 | 1216.97 | 996.34 | 779.93 | 566.09 | 350.18 | not rated |
| 60 | 1428.55 | 1206.28 | 988.86 | 775.31 | 563.91 | 349.92 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 274.58 | not rated | not rated | not rated | not rated | not rated |
| 40 | 441.64 | 273.23 | not rated | not rated | not rated | not rated |
| 45 | 603.62 | 438.26 | 272.01 | not rated | not rated | not rated |
| 50 | 763.97 | 598.43 | 435.29 | 271.01 | not rated | not rated |
| 55 | 923.59 | 757.05 | 593.88 | 432.84 | 270.32 | not rated |
| 60 | 1082.81 | 914.96 | 750.99 | 590.13 | 431.03 | 270.05 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 576.639 | 99.99 | 49.8 |
| Low speed (Y) | 441.643 | 76.60 | 31.0 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 7650 mm |
| F | 2330 mm |
| G | 8250 mm |
| E1 | 2450 mm |
| E2 | 2400 mm |
| H | 7900 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 8250 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.