BE-2x380DD5-B01T C
515.05 kW
Defrost: None
Product code: BE-2x380FB1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 132,766 m³/h |
|---|---|
| External surface | 2,460.6 m² |
| Inner volume | 460.1 dm³ |
| Fin material | Aluminium |
| Net weight | 2,448 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x380FB1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 311.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 514.62 | 310.39 | not rated | not rated | not rated | not rated |
| 45 | 712.91 | 511.86 | 309.58 | not rated | not rated | not rated |
| 50 | 909.48 | 708.40 | 509.44 | 308.94 | not rated | not rated |
| 55 | 1105.27 | 903.27 | 704.44 | 507.44 | 308.46 | not rated |
| 60 | 1300.62 | 1097.38 | 897.82 | 701.16 | 506.00 | 308.43 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 244.42 | not rated | not rated | not rated | not rated | not rated |
| 40 | 400.60 | 243.57 | not rated | not rated | not rated | not rated |
| 45 | 552.58 | 398.20 | 242.82 | not rated | not rated | not rated |
| 50 | 703.17 | 548.75 | 396.09 | 242.20 | not rated | not rated |
| 55 | 853.13 | 697.95 | 545.39 | 394.36 | 241.82 | not rated |
| 60 | 1002.74 | 846.53 | 693.37 | 542.62 | 393.13 | 241.73 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 514.619 | 89.25 | 101.3 |
| Low speed (Y) | 400.598 | 69.48 | 64.9 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 7650 mm |
| F | 2230 mm |
| G | 8250 mm |
| E1 | 2450 mm |
| E2 | 2400 mm |
| H | 7900 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 8250 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.