BE-t-2x391HB5-C04C C
561.33 kW
Defrost: None
Product code: BE-2x380FC1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 130,926 m³/h |
|---|---|
| External surface | 3,280.8 m² |
| Inner volume | 631.2 dm³ |
| Fin material | Aluminium |
| Net weight | 2,722 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x380FC1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 345.33 | not rated | not rated | not rated | not rated | not rated |
| 40 | 561.50 | 343.89 | not rated | not rated | not rated | not rated |
| 45 | 771.62 | 557.76 | 342.60 | not rated | not rated | not rated |
| 50 | 979.73 | 765.75 | 554.49 | 341.55 | not rated | not rated |
| 55 | 1186.93 | 971.81 | 760.62 | 551.79 | 340.87 | not rated |
| 60 | 1393.63 | 1176.98 | 964.88 | 756.39 | 549.84 | 340.66 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 266.40 | not rated | not rated | not rated | not rated | not rated |
| 40 | 429.01 | 265.13 | not rated | not rated | not rated | not rated |
| 45 | 586.84 | 425.91 | 264.01 | not rated | not rated | not rated |
| 50 | 743.13 | 582.07 | 423.20 | 262.98 | not rated | not rated |
| 55 | 898.73 | 736.75 | 577.91 | 420.78 | 262.40 | not rated |
| 60 | 1053.94 | 890.76 | 731.19 | 574.22 | 419.19 | 262.21 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 561.499 | 97.37 | 67.5 |
| Low speed (Y) | 429.009 | 74.41 | 41.9 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 7650 mm |
| F | 2230 mm |
| G | 8250 mm |
| E1 | 2450 mm |
| E2 | 2400 mm |
| H | 7900 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 8250 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.