BE-591ED1-B04 C
535.55 kW
Defrost: None
Product code: BE-2x380FC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 131,666 m³/h |
|---|---|
| External surface | 2,779.1 m² |
| Inner volume | 631.2 dm³ |
| Fin material | Aluminium |
| Net weight | 2,634 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x380FC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 325.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 534.96 | 324.81 | not rated | not rated | not rated | not rated |
| 45 | 738.46 | 531.81 | 323.79 | not rated | not rated | not rated |
| 50 | 940.13 | 733.41 | 529.03 | 323.01 | not rated | not rated |
| 55 | 1140.95 | 933.23 | 728.97 | 526.75 | 322.52 | not rated |
| 60 | 1341.31 | 1132.23 | 927.18 | 725.32 | 525.12 | 322.41 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 253.76 | not rated | not rated | not rated | not rated | not rated |
| 40 | 412.74 | 252.77 | not rated | not rated | not rated | not rated |
| 45 | 567.25 | 410.06 | 251.87 | not rated | not rated | not rated |
| 50 | 720.29 | 563.04 | 407.73 | 251.15 | not rated | not rated |
| 55 | 872.67 | 714.60 | 559.36 | 405.81 | 250.68 | not rated |
| 60 | 1024.68 | 865.52 | 709.63 | 556.34 | 404.44 | 250.57 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 534.957 | 92.78 | 62.0 |
| Low speed (Y) | 412.738 | 71.57 | 39.1 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 7650 mm |
| F | 2230 mm |
| G | 8250 mm |
| E1 | 2450 mm |
| E2 | 2400 mm |
| H | 7900 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 8250 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.