BE-691EC5-B04 C
568.28 kW
Defrost: None
Product code: BE-2x380FD5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 130,053 m³/h |
|---|---|
| External surface | 3,473.8 m² |
| Inner volume | 768.4 dm³ |
| Fin material | Aluminium |
| Net weight | 2,886 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x380FD5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 350.28 | not rated | not rated | not rated | not rated | not rated |
| 40 | 567.33 | 348.75 | not rated | not rated | not rated | not rated |
| 45 | 778.13 | 563.42 | 347.38 | not rated | not rated | not rated |
| 50 | 986.92 | 772.06 | 560.00 | 346.27 | not rated | not rated |
| 55 | 1194.78 | 978.75 | 766.75 | 557.20 | 345.54 | not rated |
| 60 | 1402.14 | 1184.55 | 971.62 | 762.39 | 555.18 | 345.34 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 268.98 | not rated | not rated | not rated | not rated | not rated |
| 40 | 431.41 | 267.66 | not rated | not rated | not rated | not rated |
| 45 | 589.02 | 428.21 | 266.49 | not rated | not rated | not rated |
| 50 | 745.10 | 584.14 | 425.43 | 265.55 | not rated | not rated |
| 55 | 900.48 | 738.60 | 579.90 | 423.16 | 264.93 | not rated |
| 60 | 1055.49 | 892.38 | 732.95 | 576.43 | 421.54 | 264.74 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 567.325 | 98.40 | 48.0 |
| Low speed (Y) | 431.407 | 74.83 | 29.5 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 7650 mm |
| F | 2230 mm |
| G | 8250 mm |
| E1 | 2450 mm |
| E2 | 2400 mm |
| H | 7900 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 8250 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.