Skip to Content

Dry cooler BE-2x391BC5-B04T C

Dry cooler BE-2x391BC5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x391BC5-B04T C

Heat rejection i
490.44 kW
Air flow
164,382 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 164,382 m³/h
External surface 1,313.0 m²
Inner volume 203.8 dm³
Fin materialAluminium
Net weight 1,895 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 98.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2x391BC5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
490.440 kW Fluid flow 85.12 m³/h Pressure drop 77.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
392.329 kW Fluid flow 68.09 m³/h Pressure drop 51.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 285.36 not rated not rated not rated not rated not rated
40 490.44 286.11 not rated not rated not rated not rated
45 690.90 489.87 286.78 not rated not rated not rated
50 889.88 689.16 489.40 287.39 not rated not rated
55 1088.17 887.03 687.72 489.15 288.06 not rated
60 1286.08 1084.22 884.60 686.64 489.18 288.89

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 229.86 not rated not rated not rated not rated not rated
40 392.33 230.49 not rated not rated not rated not rated
45 550.74 391.87 231.04 not rated not rated not rated
50 707.84 549.35 391.49 231.54 not rated not rated
55 864.36 705.57 548.15 391.25 232.11 not rated
60 1020.54 861.22 703.60 547.28 391.30 232.84

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 490.440 85.12 77.3
Low speed (Y) 392.329 68.09 51.9

Dimensions

Dimension drawing of BE-2x391BC5-B04T C
Dimension drawing
Dimensions as drawn
A 2910 mm
B 2400 mm
C 4050 mm
F 2330 mm
G 4650 mm
E1 1250 mm
E2 1200 mm
H 4300 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4650 mm
Width 2400 mm
Height 2910 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.