Skip to Content

Dry cooler BE-2x391FC5-C04C C

Dry cooler BE-2x391FC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x391FC5-C04C C

Heat rejection i
658.67 kW
Air flow
172,293 m³/h
Fans
6 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 172,293 m³/h
External surface 2,665.5 m²
Inner volume 605.5 dm³
Fin materialAluminium
Net weight 2,665 kg
Fans
Quantity 6
Diameter 910 mm
Speed 840 rpm
Power 16,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 98.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x391FC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
658.671 kW Fluid flow 114.24 m³/h Pressure drop 96.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
518.025 kW Fluid flow 89.84 m³/h Pressure drop 62.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 397.70 not rated not rated not rated not rated not rated
40 658.67 396.82 not rated not rated not rated not rated
45 913.21 655.54 396.00 not rated not rated not rated
50 1165.60 908.03 652.81 395.39 not rated not rated
55 1417.00 1158.40 903.49 650.65 395.05 not rated
60 1667.86 1407.80 1152.11 899.83 649.16 395.17

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 315.46 not rated not rated not rated not rated not rated
40 518.03 314.57 not rated not rated not rated not rated
45 715.21 515.26 313.78 not rated not rated not rated
50 910.61 710.72 512.86 313.19 not rated not rated
55 1105.20 904.45 706.83 510.94 312.86 not rated
60 1299.35 1097.39 899.11 703.69 509.65 312.95

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 658.671 114.24 96.0
Low speed (Y) 518.025 89.84 62.7

Dimensions

Dimension drawing of BE-2x391FC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 7650 mm
F 2230 mm
G 8250 mm
E1 2450 mm
E2 2400 mm
H 7900 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.