Skip to Content

Dry cooler BE-2x480AB5-B01T C

Dry cooler BE-2x480AB5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480AB5-B01T C

Heat rejection i
499.27 kW
Air flow
171,391 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 171,391 m³/h
External surface 1,700.1 m²
Inner volume 297.7 dm³
Fin materialAluminium
Net weight 2,344 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x480AB5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
499.269 kW Fluid flow 86.65 m³/h Pressure drop 61.3 kPa
Heat rejection · Low speed (Y)
402.140 kW Fluid flow 69.80 m³/h Pressure drop 41.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 289.43 not rated not rated not rated not rated not rated
40 499.27 290.12 not rated not rated not rated not rated
45 704.61 498.59 290.70 not rated not rated not rated
50 908.51 702.67 497.99 291.28 not rated not rated
55 1111.71 905.35 700.98 497.57 291.88 not rated
60 1314.54 1107.37 902.61 699.67 497.47 292.62

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 234.95 not rated not rated not rated not rated not rated
40 402.14 235.41 not rated not rated not rated not rated
45 565.34 401.37 235.79 not rated not rated not rated
50 727.25 563.47 400.71 236.18 not rated not rated
55 888.55 724.33 561.88 400.25 236.62 not rated
60 1049.53 884.61 721.82 560.63 400.06 237.21

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 499.269 86.65 61.3
Low speed (Y) 402.140 69.80 41.8

Dimensions

Dimension drawing of BE-2x480AB5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 5250 mm
F 2330 mm
G 5850 mm
E1 1250 mm
E2 2400 mm
H 5500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5850 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.