Skip to Content

Dry cooler BE-2x480BD5-B01T C

Dry cooler BE-2x480BD5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480BD5-B01T C

Heat rejection i
580.19 kW
Air flow
161,940 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): D — 5 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): T — T: truck delivery version

Data

Coil
Air flow 161,940 m³/h
External surface 2,005.7 m²
Inner volume 320.4 dm³
Fin materialAluminium
Net weight 2,431 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x480BD5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
580.188 kW Fluid flow 100.69 m³/h Pressure drop 77.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
448.528 kW Fluid flow 77.79 m³/h Pressure drop 49.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 345.61 not rated not rated not rated not rated not rated
40 580.19 345.70 not rated not rated not rated not rated
45 808.78 578.52 345.78 not rated not rated not rated
50 1035.49 805.52 577.13 345.95 not rated not rated
55 1261.33 1030.72 802.78 576.02 346.34 not rated
60 1486.65 1255.05 1026.66 800.68 575.58 347.02

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 269.48 not rated not rated not rated not rated not rated
40 448.53 269.54 not rated not rated not rated not rated
45 622.64 447.12 269.58 not rated not rated not rated
50 795.16 620.00 445.98 269.74 not rated not rated
55 966.92 791.30 617.79 445.19 270.01 not rated
60 1138.27 961.89 788.08 616.17 444.87 270.62

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 580.188 100.69 77.9
Low speed (Y) 448.528 77.79 49.3

Dimensions

Dimension drawing of BE-2x480BD5-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 4850 mm
F 2330 mm
G 5450 mm
E1 1150 mm
E2 2200 mm
H 5100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5450 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.