BE-t-2x580GB5-B01T C
691.99 kW
Defrost: None
Product code: BE-2x480CC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 177,365 m³/h |
|---|---|
| External surface | 3,896.8 m² |
| Inner volume | 549.2 dm³ |
| Fin material | Aluminium |
| Net weight | 3,279 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x480CC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 416.85 | not rated | not rated | not rated | not rated | not rated |
| 40 | 691.50 | 415.91 | not rated | not rated | not rated | not rated |
| 45 | 958.90 | 687.93 | 415.08 | not rated | not rated | not rated |
| 50 | 1223.84 | 952.86 | 684.75 | 414.29 | not rated | not rated |
| 55 | 1487.65 | 1215.43 | 947.53 | 682.13 | 413.92 | not rated |
| 60 | 1750.84 | 1476.91 | 1208.03 | 943.13 | 680.25 | 413.98 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 327.98 | not rated | not rated | not rated | not rated | not rated |
| 40 | 539.20 | 327.07 | not rated | not rated | not rated | not rated |
| 45 | 744.29 | 536.03 | 326.20 | not rated | not rated | not rated |
| 50 | 947.38 | 739.11 | 533.23 | 325.53 | not rated | not rated |
| 55 | 1149.54 | 940.25 | 734.55 | 530.95 | 325.12 | not rated |
| 60 | 1351.20 | 1140.50 | 933.99 | 730.79 | 529.31 | 325.11 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 691.499 | 119.92 | 58.2 |
| Low speed (Y) | 539.199 | 93.51 | 37.4 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 10050 mm |
| F | 2230 mm |
| G | 10650 mm |
| E1 | 2450 mm |
| E2 | 4800 mm |
| H | 10300 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 10650 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.