Dry cooler BE-2x491CB1-B04T C

Dry cooler BE-2x491CB1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x491CB1-B04T C

Heat rejection i
856.04 kW
Air flow
238,951 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): T — T: truck delivery version

Data

Coil
Air flow 238,951 m³/h
External surface 4,021.8 m²
Inner volume 502.0 dm³
Fin materialAluminium
Net weight 3,454 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x491CB1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
856.035 kW Fluid flow 148.56 m³/h Pressure drop 105.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
683.918 kW Fluid flow 118.62 m³/h Pressure drop 70.6 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 510.33 not rated not rated not rated not rated not rated
40 856.04 509.66 not rated not rated not rated not rated
45 1193.27 852.44 509.00 not rated not rated not rated
50 1527.83 1186.93 849.24 508.55 not rated not rated
55 1861.14 1518.83 1181.33 846.48 508.35 not rated
60 2193.69 1849.47 1510.87 1176.69 844.68 508.64

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 411.22 not rated not rated not rated not rated not rated
40 683.92 410.43 not rated not rated not rated not rated
45 949.52 680.54 409.64 not rated not rated not rated
50 1212.80 943.82 677.55 409.06 not rated not rated
55 1474.95 1204.78 938.73 675.08 408.62 not rated
60 1736.49 1464.68 1197.68 934.54 673.32 408.74

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 856.035 148.56 105.3
Low speed (Y) 683.918 118.62 70.6

Dimensions

Dimension drawing of BE-2x491CB1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.