Skip to Content

Dry cooler BE-2x491FB1-B04T C

Dry cooler BE-2x491FB1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x491FB1-B04T C

Heat rejection i
876.05 kW
Air flow
236,691 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 236,691 m³/h
External surface 3,816.9 m²
Inner volume 733.9 dm³
Fin materialAluminium
Net weight 3,578 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 99.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x491FB1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
876.050 kW Fluid flow 151.91 m³/h Pressure drop 45.0 kPa
Heat rejection · Low speed (Y)
693.631 kW Fluid flow 120.31 m³/h Pressure drop 29.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 520.14 not rated not rated not rated not rated not rated
40 876.05 519.95 not rated not rated not rated not rated
45 1222.61 872.59 519.75 not rated not rated not rated
50 1565.94 1216.08 869.49 519.60 not rated not rated
55 1907.80 1556.50 1210.33 866.96 519.76 not rated
60 2248.84 1895.51 1548.24 1205.65 865.29 520.36

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 415.36 not rated not rated not rated not rated not rated
40 693.63 414.98 not rated not rated not rated not rated
45 963.84 690.41 414.59 not rated not rated not rated
50 1231.36 958.08 687.55 414.22 not rated not rated
55 1497.63 1223.16 953.02 685.24 414.20 not rated
60 1763.20 1487.05 1215.99 948.89 683.67 414.60

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 876.050 151.91 45.0
Low speed (Y) 693.631 120.31 29.6

Dimensions

Dimension drawing of BE-2x491FB1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.