BE-980AC5-B01 C
661.84 kW
Defrost: None
Product code: BE-2x580EB5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 210,254 m³/h |
|---|---|
| External surface | 2,020.8 m² |
| Inner volume | 493.7 dm³ |
| Fin material | Aluminium |
| Net weight | 2,920 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x580EB5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 390.62 | not rated | not rated | not rated | not rated | not rated |
| 40 | 663.02 | 390.84 | not rated | not rated | not rated | not rated |
| 45 | 929.56 | 661.52 | 391.02 | not rated | not rated | not rated |
| 50 | 1194.17 | 926.44 | 660.23 | 391.31 | not rated | not rated |
| 55 | 1457.92 | 1189.50 | 923.77 | 659.30 | 391.73 | not rated |
| 60 | 1721.15 | 1451.68 | 1185.48 | 921.74 | 658.88 | 392.43 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 312.54 | not rated | not rated | not rated | not rated | not rated |
| 40 | 526.25 | 312.53 | not rated | not rated | not rated | not rated |
| 45 | 734.98 | 524.72 | 312.52 | not rated | not rated | not rated |
| 50 | 942.05 | 732.05 | 523.44 | 312.62 | not rated | not rated |
| 55 | 1148.30 | 937.70 | 729.48 | 522.48 | 312.87 | not rated |
| 60 | 1354.20 | 1142.68 | 934.04 | 727.56 | 522.01 | 313.40 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 663.024 | 115.08 | 96.1 |
| Low speed (Y) | 526.252 | 91.33 | 63.8 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 6450 mm |
| F | 2330 mm |
| G | 7050 mm |
| E1 | 1250 mm |
| E2 | 3600 mm |
| H | 6700 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7050 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.