BE-t-2x391HB5-B04T C
605.75 kW
Defrost: None
Product code: BE-2x591BB5-C04C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 272,482 m³/h |
|---|---|
| External surface | 1,342.8 m² |
| Inner volume | 231.4 dm³ |
| Fin material | Aluminium |
| Net weight | 2,473 kg |
| Quantity | 10 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 28,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 67.0 dB(A) |
|---|---|
| Sound power | 100.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x591BB5-C04C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 333.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 605.71 | 336.75 | not rated | not rated | not rated | not rated |
| 45 | 871.94 | 607.57 | 339.94 | not rated | not rated | not rated |
| 50 | 1136.32 | 872.43 | 609.20 | 342.70 | not rated | not rated |
| 55 | 1399.83 | 1135.59 | 872.93 | 610.77 | 345.21 | not rated |
| 60 | 1662.94 | 1397.95 | 1135.06 | 873.64 | 612.46 | 347.61 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 273.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 494.60 | 276.34 | not rated | not rated | not rated | not rated |
| 45 | 709.97 | 496.21 | 279.11 | not rated | not rated | not rated |
| 50 | 923.49 | 710.41 | 497.63 | 281.54 | not rated | not rated |
| 55 | 1136.26 | 922.98 | 710.91 | 499.03 | 283.77 | not rated |
| 60 | 1348.56 | 1134.79 | 922.66 | 711.60 | 500.55 | 285.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 605.708 | 105.13 | 22.5 |
| Low speed (Y) | 494.598 | 85.83 | 15.6 |
| A | 2511 mm |
|---|---|
| B | 2300 mm |
| C | 6450 mm |
| F | 2230 mm |
| G | 7050 mm |
| E1 | 1230 mm |
| E2 | 3600 mm |
| H | 6700 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2511 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.