Skip to Content

Dry cooler BE-2x591BB5-C04C C

Dry cooler BE-2x591BB5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x591BB5-C04C C

Heat rejection i
605.71 kW
Air flow
272,482 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 272,482 m³/h
External surface 1,342.8 m²
Inner volume 231.4 dm³
Fin materialAluminium
Net weight 2,473 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 100.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x591BB5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
605.708 kW Fluid flow 105.13 m³/h Pressure drop 22.5 kPa
Heat rejection · Low speed (Y)
494.598 kW Fluid flow 85.83 m³/h Pressure drop 15.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 333.01 not rated not rated not rated not rated not rated
40 605.71 336.75 not rated not rated not rated not rated
45 871.94 607.57 339.94 not rated not rated not rated
50 1136.32 872.43 609.20 342.70 not rated not rated
55 1399.83 1135.59 872.93 610.77 345.21 not rated
60 1662.94 1397.95 1135.06 873.64 612.46 347.61

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 273.01 not rated not rated not rated not rated not rated
40 494.60 276.34 not rated not rated not rated not rated
45 709.97 496.21 279.11 not rated not rated not rated
50 923.49 710.41 497.63 281.54 not rated not rated
55 1136.26 922.98 710.91 499.03 283.77 not rated
60 1348.56 1134.79 922.66 711.60 500.55 285.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 605.708 105.13 22.5
Low speed (Y) 494.598 85.83 15.6

Dimensions

Dimension drawing of BE-2x591BB5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 6450 mm
F 2230 mm
G 7050 mm
E1 1230 mm
E2 3600 mm
H 6700 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6450 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.