Dry cooler BE-2x591BC1-B04T C

Dry cooler BE-2x591BC1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x591BC1-B04T C

Heat rejection i
892.02 kW
Air flow
270,801 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 270,801 m³/h
External surface 2,583.7 m²
Inner volume 342.2 dm³
Fin materialAluminium
Net weight 3,001 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 100.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x591BC1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
892.021 kW Fluid flow 154.81 m³/h Pressure drop 111.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
704.064 kW Fluid flow 122.19 m³/h Pressure drop 73.0 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 524.91 not rated not rated not rated not rated not rated
40 892.02 525.64 not rated not rated not rated not rated
45 1250.54 890.18 526.23 not rated not rated not rated
50 1606.16 1246.39 888.67 526.88 not rated not rated
55 1960.52 1599.84 1242.88 887.60 527.74 not rated
60 2314.14 1952.02 1594.46 1240.27 887.23 529.03

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 417.66 not rated not rated not rated not rated not rated
40 704.06 418.27 not rated not rated not rated not rated
45 982.98 702.63 418.80 not rated not rated not rated
50 1259.54 979.75 701.47 419.42 not rated not rated
55 1535.02 1254.62 977.11 700.71 420.28 not rated
60 1809.85 1528.40 1250.53 975.26 700.65 421.48

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 892.021 154.81 111.2
Low speed (Y) 704.064 122.19 73.0

Dimensions

Dimension drawing of BE-2x591BC1-B04T C
Dimension drawing
Dimensions as drawn
A 2910 mm
B 2400 mm
C 6450 mm
F 2330 mm
G 7050 mm
E1 1250 mm
E2 3600 mm
H 6700 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7050 mm
Width 2400 mm
Height 2910 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.