Skip to Content

Dry cooler BE-2x591EC5-B04T C

Dry cooler BE-2x591EC5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x591EC5-B04T C

Heat rejection i
905.38 kW
Air flow
263,472 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 263,472 m³/h
External surface 2,694.4 m²
Inner volume 676.0 dm³
Fin materialAluminium
Net weight 3,223 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 100.3 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x591EC5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
905.381 kW Fluid flow 157.13 m³/h Pressure drop 98.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
708.625 kW Fluid flow 122.90 m³/h Pressure drop 63.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 537.16 not rated not rated not rated not rated not rated
40 905.38 537.42 not rated not rated not rated not rated
45 1265.09 903.26 537.69 not rated not rated not rated
50 1621.96 1260.77 901.56 538.15 not rated not rated
55 1977.42 1615.39 1257.08 900.39 538.86 not rated
60 2332.28 1968.85 1609.98 1254.42 900.07 540.05

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 424.38 not rated not rated not rated not rated not rated
40 708.63 424.56 not rated not rated not rated not rated
45 985.77 706.88 424.76 not rated not rated not rated
50 1260.53 982.28 705.52 425.16 not rated not rated
55 1534.19 1255.37 979.47 704.68 425.81 not rated
60 1807.23 1527.38 1251.19 977.58 704.62 426.95

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 905.381 157.13 98.3
Low speed (Y) 708.625 122.90 63.7

Dimensions

Dimension drawing of BE-2x591EC5-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 6450 mm
F 2330 mm
G 7050 mm
E1 1250 mm
E2 3600 mm
H 6700 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 7050 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.