Skip to Content

Dry cooler BE-2x680AD5-B01T C

Dry cooler BE-2x680AD5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x680AD5-B01T C

Heat rejection i
931.54 kW
Air flow
244,708 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 244,708 m³/h
External surface 4,250.3 m²
Inner volume 653.1 dm³
Fin materialAluminium
Net weight 4,077 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 91.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x680AD5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
931.536 kW Fluid flow 161.57 m³/h Pressure drop 38.9 kPa
Heat rejection · Low speed (Y)
719.038 kW Fluid flow 124.70 m³/h Pressure drop 24.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 553.85 not rated not rated not rated not rated not rated
40 931.54 554.29 not rated not rated not rated not rated
45 1298.47 928.57 554.61 not rated not rated not rated
50 1661.87 1292.58 926.08 555.07 not rated not rated
55 2023.56 1653.10 1287.52 924.23 555.85 not rated
60 2384.33 2012.03 1645.62 1283.63 923.31 556.97

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 432.02 not rated not rated not rated not rated not rated
40 719.04 432.23 not rated not rated not rated not rated
45 997.01 716.49 432.44 not rated not rated not rated
50 1271.96 992.10 714.35 432.75 not rated not rated
55 1545.52 1264.82 987.97 712.85 433.36 not rated
60 1818.32 1536.22 1258.81 984.87 712.16 434.45

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 931.536 161.57 38.9
Low speed (Y) 719.038 124.70 24.5

Dimensions

Dimension drawing of BE-2x680AD5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 7650 mm
F 2330 mm
G 8250 mm
E1 1250 mm
E2 1200 mm
E3 2400 mm
H 7900 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8250 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.