Skip to Content

Dry cooler BE-2x680BC5-B01C C

Dry cooler BE-2x680BC5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x680BC5-B01C C

Heat rejection i
737.39 kW
Air flow
240,828 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 240,828 m³/h
External surface 2,032.1 m²
Inner volume 311.4 dm³
Fin materialAluminium
Net weight 3,089 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 91.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x680BC5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
737.388 kW Fluid flow 127.96 m³/h Pressure drop 113.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
580.336 kW Fluid flow 100.73 m³/h Pressure drop 74.3 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 433.17 not rated not rated not rated not rated not rated
40 737.39 433.94 not rated not rated not rated not rated
45 1035.00 736.48 434.63 not rated not rated not rated
50 1330.47 1032.54 735.75 435.29 not rated not rated
55 1624.94 1326.49 1030.52 735.26 436.11 not rated
60 1918.89 1619.54 1323.22 1028.96 735.26 437.24

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 343.47 not rated not rated not rated not rated not rated
40 580.34 343.97 not rated not rated not rated not rated
45 811.52 579.36 344.44 not rated not rated not rated
50 1040.87 809.24 578.61 344.98 not rated not rated
55 1269.40 1037.35 807.41 578.21 345.71 not rated
60 1497.35 1264.58 1034.39 806.18 578.31 346.68

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 737.388 127.96 113.5
Low speed (Y) 580.336 100.73 74.3

Dimensions

Dimension drawing of BE-2x680BC5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 7050 mm
F 2230 mm
G 7650 mm
E1 1150 mm
E2 1100 mm
E3 2200 mm
H 7300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.