Heat rejection i
742.02 kW
Air flow
245,534 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 245,534 m³/h
External surface 2,084.3 m²
Inner volume 493.9 dm³
Fin materialAluminium
Net weight 3,248 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 91.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x680EB5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
742.024 kW Fluid flow 128.77 m³/h Pressure drop 84.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
588.811 kW Fluid flow 102.18 m³/h Pressure drop 56.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 434.10 not rated not rated not rated not rated not rated
40 742.02 434.82 not rated not rated not rated not rated
45 1043.49 740.96 435.46 not rated not rated not rated
50 1342.85 1040.75 740.12 436.13 not rated not rated
55 1641.21 1338.49 1038.49 739.58 436.95 not rated
60 1939.06 1635.26 1334.82 1036.83 739.55 438.05

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 347.24 not rated not rated not rated not rated not rated
40 588.81 347.76 not rated not rated not rated not rated
45 824.82 587.82 348.20 not rated not rated not rated
50 1058.97 822.41 587.00 348.71 not rated not rated
55 1292.27 1055.22 820.45 586.52 349.39 not rated
60 1525.10 1287.22 1052.14 819.06 586.55 350.36

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 742.024 128.77 84.8
Low speed (Y) 588.811 102.18 56.2

Dimensions

Dimension drawing of BE-2x680EB5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 7650 mm
F 2230 mm
G 8250 mm
E1 1250 mm
E2 1200 mm
E3 2400 mm
H 7900 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 8250 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.