Dry cooler BE-2x691EC1-B04T C

Dry cooler BE-2x691EC1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x691EC1-B04T C

Heat rejection i
1151.66 kW
Air flow
311,085 m³/h
Fans
12 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 311,085 m³/h
External surface 3,815.4 m²
Inner volume 777.0 dm³
Fin materialAluminium
Net weight 4,087 kg
Fans
Quantity 12
Diameter 910 mm
Speed 840 rpm
Power 33,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 69.0 dB(A)
Sound power 101.5 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x691EC1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1151.660 kW Fluid flow 199.74 m³/h Pressure drop 85.7 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
888.657 kW Fluid flow 154.13 m³/h Pressure drop 54.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 686.03 not rated not rated not rated not rated not rated
40 1151.66 686.35 not rated not rated not rated not rated
45 1605.51 1148.60 686.73 not rated not rated not rated
50 2055.35 1599.30 1146.09 687.27 not rated not rated
55 2503.34 2046.12 1594.14 1144.38 688.30 not rated
60 2950.28 2491.15 2038.47 1590.43 1143.87 689.97

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 534.95 not rated not rated not rated not rated not rated
40 888.66 535.12 not rated not rated not rated not rated
45 1232.59 886.16 535.24 not rated not rated not rated
50 1573.20 1227.69 884.20 535.75 not rated not rated
55 1912.27 1566.01 1223.74 883.01 536.67 not rated
60 2250.48 1902.84 1560.17 1221.06 882.85 538.20

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1151.660 199.74 85.7
Low speed (Y) 888.657 154.13 54.1

Dimensions

Dimension drawing of BE-2x691EC1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 7650 mm
F 2330 mm
G 8250 mm
E1 1250 mm
E2 1200 mm
E3 2400 mm
H 7900 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8250 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.