Skip to Content

Dry cooler BE-2x780AB5-B01C C

Dry cooler BE-2x780AB5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x780AB5-B01C C

Heat rejection i
824.63 kW
Air flow
293,532 m³/h
Fans
14 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 293,532 m³/h
External surface 2,557.3 m²
Inner volume 431.8 dm³
Fin materialAluminium
Net weight 3,613 kg
Fans
Quantity 14
Diameter 800 mm
Speed 900 rpm
Power 25,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x780AB5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
824.626 kW Fluid flow 143.13 m³/h Pressure drop 105.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
665.847 kW Fluid flow 115.57 m³/h Pressure drop 72.6 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 479.79 not rated not rated not rated not rated not rated
40 824.63 480.76 not rated not rated not rated not rated
45 1162.59 823.67 481.55 not rated not rated not rated
50 1498.29 1159.84 822.87 482.38 not rated not rated
55 1833.01 1493.80 1157.49 822.37 483.36 not rated
60 2167.12 1826.82 1490.01 1155.76 822.36 484.55

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 390.35 not rated not rated not rated not rated not rated
40 665.85 391.00 not rated not rated not rated not rated
45 935.25 664.79 391.48 not rated not rated not rated
50 1202.65 932.63 663.77 392.00 not rated not rated
55 1469.18 1198.57 930.23 663.09 392.69 not rated
60 1735.17 1463.59 1194.82 928.44 662.89 393.61

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 824.626 143.13 105.9
Low speed (Y) 665.847 115.57 72.6

Dimensions

Dimension drawing of BE-2x780AB5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 8850 mm
F 2230 mm
G 9450 mm
E1 1250 mm
E2 1200 mm
E3 3600 mm
H 9100 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 9450 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.