Skip to Content

Dry cooler BE-2x880EC5-B01C C

Dry cooler BE-2x880EC5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x880EC5-B01C C

Heat rejection i
1109.46 kW
Air flow
314,575 m³/h
Fans
16 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 314,575 m³/h
External surface 3,705.4 m²
Inner volume 857.3 dm³
Fin materialAluminium
Net weight 4,518 kg
Fans
Quantity 16
Diameter 800 mm
Speed 900 rpm
Power 28,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x880EC5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1109.458 kW Fluid flow 192.57 m³/h Pressure drop 47.8 kPa
Heat rejection · Low speed (Y)
859.170 kW Fluid flow 149.02 m³/h Pressure drop 30.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 654.83 not rated not rated not rated not rated not rated
40 1109.46 655.92 not rated not rated not rated not rated
45 1552.39 1107.33 656.96 not rated not rated not rated
50 1991.73 1547.42 1105.68 658.06 not rated not rated
55 2429.29 1984.01 1543.35 1104.72 659.48 not rated
60 2865.82 2418.84 1977.60 1540.52 1104.60 661.51

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 512.18 not rated not rated not rated not rated not rated
40 859.17 512.77 not rated not rated not rated not rated
45 1196.56 857.06 513.38 not rated not rated not rated
50 1530.79 1192.11 855.40 514.10 not rated not rated
55 1863.48 1524.02 1188.48 854.46 515.19 not rated
60 2195.34 1854.50 1518.52 1186.00 854.38 516.64

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1109.458 192.57 47.8
Low speed (Y) 859.170 149.02 30.2

Dimensions

Dimension drawing of BE-2x880EC5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.