Skip to Content

Dry cooler BE-2x891AB5-C04C C

Dry cooler BE-2x891AB5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x891AB5-C04C C

Heat rejection i
1046.17 kW
Air flow
432,383 m³/h
Fans
16 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 432,383 m³/h
External surface 2,803.2 m²
Inner volume 456.7 dm³
Fin materialAluminium
Net weight 4,158 kg
Fans
Quantity 16
Diameter 910 mm
Speed 840 rpm
Power 44,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 70.0 dB(A)
Sound power 103.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x891AB5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1046.168 kW Fluid flow 181.55 m³/h Pressure drop 34.1 kPa
Heat rejection · Low speed (Y)
857.761 kW Fluid flow 148.86 m³/h Pressure drop 23.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 585.06 not rated not rated not rated not rated not rated
40 1046.17 589.64 not rated not rated not rated not rated
45 1498.12 1048.18 593.61 not rated not rated not rated
50 1947.08 1497.82 1049.87 597.10 not rated not rated
55 2394.81 1944.67 1497.58 1051.60 600.39 not rated
60 2841.72 2390.36 1942.62 1497.79 1053.64 603.69

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 483.14 not rated not rated not rated not rated not rated
40 857.76 486.96 not rated not rated not rated not rated
45 1223.70 859.26 490.26 not rated not rated not rated
50 1586.92 1223.36 860.68 493.26 not rated not rated
55 1948.84 1584.76 1223.21 862.28 496.19 not rated
60 2310.10 1945.06 1583.16 1223.56 864.18 499.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1046.168 181.55 34.1
Low speed (Y) 857.761 148.86 23.9

Dimensions

Dimension drawing of BE-2x891AB5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10050 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.