Dry cooler BE-2x891EC5-B04T C

Dry cooler BE-2x891EC5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x891EC5-B04T C

Heat rejection i
1432.74 kW
Air flow
421,556 m³/h
Fans
16 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 421,556 m³/h
External surface 4,311.0 m²
Inner volume 1,057.3 dm³
Fin materialAluminium
Net weight 5,146 kg
Fans
Quantity 16
Diameter 910 mm
Speed 840 rpm
Power 44,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 70.0 dB(A)
Sound power 103.3 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BE-2x891EC5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1432.744 kW Fluid flow 248.68 m³/h Pressure drop 54.3 kPa
Heat rejection · Low speed (Y)
1122.375 kW Fluid flow 194.79 m³/h Pressure drop 35.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 842.29 not rated not rated not rated not rated not rated
40 1432.74 843.79 not rated not rated not rated not rated
45 2008.89 1430.23 845.14 not rated not rated not rated
50 2580.40 2002.76 1428.20 846.60 not rated not rated
55 3149.50 2570.53 1997.70 1427.04 848.49 not rated
60 3717.55 3136.40 2562.51 1993.90 1427.04 850.94

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 666.07 not rated not rated not rated not rated not rated
40 1122.38 667.19 not rated not rated not rated not rated
45 1566.37 1120.10 668.30 not rated not rated not rated
50 2006.43 1561.36 1118.49 669.50 not rated not rated
55 2444.61 1998.68 1557.35 1117.68 671.13 not rated
60 2881.74 2434.18 1992.39 1554.74 1117.93 673.38

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1432.744 248.68 54.3
Low speed (Y) 1122.375 194.79 35.1

Dimensions

Dimension drawing of BE-2x891EC5-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.