BE-2X880AC1-B01C C
1120.82 kW
Defrost: None
Product code: BE-2x980AB1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 373,228 m³/h |
|---|---|
| External surface | 3,889.1 m² |
| Inner volume | 519.3 dm³ |
| Fin material | Aluminium |
| Net weight | 4,619 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x980AB1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 643.90 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1126.78 | 647.15 | not rated | not rated | not rated | not rated |
| 45 | 1598.14 | 1126.56 | 649.92 | not rated | not rated | not rated |
| 50 | 2065.80 | 1594.89 | 1126.42 | 652.46 | not rated | not rated |
| 55 | 2531.67 | 2059.65 | 1592.21 | 1126.67 | 655.06 | not rated |
| 60 | 2996.62 | 2522.78 | 2054.44 | 1590.30 | 1127.47 | 657.83 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 519.04 | not rated | not rated | not rated | not rated | not rated |
| 40 | 900.25 | 521.53 | not rated | not rated | not rated | not rated |
| 45 | 1271.08 | 899.71 | 523.66 | not rated | not rated | not rated |
| 50 | 1638.46 | 1267.96 | 899.35 | 525.69 | not rated | not rated |
| 55 | 2004.20 | 1632.96 | 1265.41 | 899.33 | 527.73 | not rated |
| 60 | 2369.11 | 1996.33 | 1628.26 | 1263.69 | 899.97 | 530.04 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1126.777 | 195.56 | 40.4 |
| Low speed (Y) | 900.247 | 156.24 | 27.0 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 11250 mm |
| F | 2230 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.