BE-2x980EB1-B01C C
1205.36 kW
Defrost: None
Product code: BE-2x980AB1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 382,563 m³/h |
|---|---|
| External surface | 4,524.5 m² |
| Inner volume | 602.0 dm³ |
| Fin material | Aluminium |
| Net weight | 5,162 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x980AB1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 689.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1202.08 | 692.37 | not rated | not rated | not rated | not rated |
| 45 | 1702.01 | 1201.10 | 694.98 | not rated | not rated | not rated |
| 50 | 2197.70 | 1697.36 | 1200.12 | 697.27 | not rated | not rated |
| 55 | 2691.37 | 2189.62 | 1693.27 | 1199.54 | 699.59 | not rated |
| 60 | 3184.01 | 2680.04 | 2182.56 | 1690.20 | 1199.69 | 702.19 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 554.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 958.45 | 556.73 | not rated | not rated | not rated | not rated |
| 45 | 1350.77 | 957.06 | 558.64 | not rated | not rated | not rated |
| 50 | 1739.20 | 1346.35 | 955.89 | 560.35 | not rated | not rated |
| 55 | 2125.98 | 1731.85 | 1342.37 | 955.15 | 562.14 | not rated |
| 60 | 2511.74 | 2115.84 | 1725.55 | 1339.47 | 955.10 | 564.27 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1202.080 | 208.61 | 36.8 |
| Low speed (Y) | 958.454 | 166.35 | 24.5 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 11250 mm |
| F | 2330 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.