Skip to Content

Dry cooler BE-2x980AB5-B01C C

Dry cooler BE-2x980AB5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x980AB5-B01C C

Heat rejection i
1030.36 kW
Air flow
377,398 m³/h
Fans
18 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 377,398 m³/h
External surface 3,288.0 m²
Inner volume 519.3 dm³
Fin materialAluminium
Net weight 4,521 kg
Fans
Quantity 18
Diameter 800 mm
Speed 900 rpm
Power 32,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 94.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x980AB5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1030.357 kW Fluid flow 178.81 m³/h Pressure drop 34.4 kPa
Heat rejection · Low speed (Y)
833.092 kW Fluid flow 144.58 m³/h Pressure drop 23.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 585.24 not rated not rated not rated not rated not rated
40 1030.36 588.57 not rated not rated not rated not rated
45 1465.71 1030.77 591.45 not rated not rated not rated
50 1897.98 1463.67 1031.21 594.00 not rated not rated
55 2328.77 1893.48 1461.89 1031.79 596.48 not rated
60 2758.82 2322.02 1889.66 1460.72 1032.81 599.08

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 476.76 not rated not rated not rated not rated not rated
40 833.09 479.35 not rated not rated not rated not rated
45 1180.42 833.07 481.46 not rated not rated not rated
50 1524.89 1178.24 832.90 483.42 not rated not rated
55 1868.06 1520.60 1176.13 833.05 485.32 not rated
60 2210.43 1861.76 1516.66 1174.68 833.63 487.40

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1030.357 178.81 34.4
Low speed (Y) 833.092 144.58 23.5

Dimensions

Dimension drawing of BE-2x980AB5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 11250 mm
F 2230 mm
G 11850 mm
E1 1250 mm
E2 2400 mm
E3 3600 mm
H 11500 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 11850 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.