BE-2x891EC1-B04T C
1526.99 kW
Defrost: None
Product code: BE-2x991EB1-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 485,932 m³/h |
|---|---|
| External surface | 4,294.0 m² |
| Inner volume | 923.8 dm³ |
| Fin material | Aluminium |
| Net weight | 5,382 kg |
| Quantity | 18 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 50,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 104.0 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BE-2x991EB1-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 908.12 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1548.06 | 909.42 | not rated | not rated | not rated | not rated |
| 45 | 2173.95 | 1545.42 | 910.47 | not rated | not rated | not rated |
| 50 | 2795.26 | 2167.62 | 1543.05 | 911.71 | not rated | not rated |
| 55 | 3414.34 | 2785.34 | 2162.05 | 1541.47 | 913.22 | not rated |
| 60 | 4032.31 | 3400.99 | 2776.64 | 2157.95 | 1541.10 | 915.37 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 728.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1230.28 | 728.92 | not rated | not rated | not rated | not rated |
| 45 | 1720.54 | 1228.01 | 729.80 | not rated | not rated | not rated |
| 50 | 2206.60 | 1715.22 | 1226.17 | 730.90 | not rated | not rated |
| 55 | 2690.98 | 2198.47 | 1710.79 | 1225.14 | 732.33 | not rated |
| 60 | 3174.28 | 2680.00 | 2191.75 | 1707.86 | 1225.13 | 734.39 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1548.059 | 268.69 | 110.2 |
| Low speed (Y) | 1230.279 | 213.51 | 73.3 |
| A | 2880 mm |
|---|---|
| B | 2400 mm |
| C | 11250 mm |
| F | 2330 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 11850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2880 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.