BE-2x191CC1-B04T C
238.44 kW
Defrost: None
Product code: BE-380BD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 61,022 m³/h |
|---|---|
| External surface | 969.1 m² |
| Inner volume | 118.6 dm³ |
| Fin material | Aluminium |
| Net weight | 879 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-380BD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 143.77 | not rated | not rated | not rated | not rated | not rated |
| 40 | 238.75 | 143.66 | not rated | not rated | not rated | not rated |
| 45 | 331.15 | 237.82 | 143.56 | not rated | not rated | not rated |
| 50 | 422.68 | 329.47 | 237.02 | 143.49 | not rated | not rated |
| 55 | 513.80 | 420.28 | 328.04 | 236.41 | 143.56 | not rated |
| 60 | 604.71 | 510.72 | 418.25 | 326.93 | 236.07 | 143.78 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 110.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 182.48 | 110.78 | not rated | not rated | not rated | not rated |
| 45 | 251.92 | 181.71 | 110.69 | not rated | not rated | not rated |
| 50 | 320.66 | 250.58 | 181.07 | 110.67 | not rated | not rated |
| 55 | 389.08 | 318.77 | 249.45 | 180.61 | 110.73 | not rated |
| 60 | 457.32 | 386.65 | 317.18 | 248.60 | 180.37 | 110.93 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 238.748 | 41.40 | 78.4 |
| Low speed (Y) | 182.475 | 31.64 | 48.7 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 3760 mm |
| F | 1050 mm |
| G | 4360 mm |
| E1 | 1130 mm |
| E2 | 1100 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4360 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |