Skip to Content

Dry cooler BE-380BD1-B01 C

Dry cooler BE-380BD1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-380BD1-B01 C

Heat rejection i
238.75 kW
Air flow
61,022 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 61,022 m³/h
External surface 969.1 m²
Inner volume 118.6 dm³
Fin materialAluminium
Net weight 879 kg
Fans
Quantity 3
Diameter 800 mm
Speed 900 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 85.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-380BD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
238.748 kW Fluid flow 41.40 m³/h Pressure drop 78.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
182.475 kW Fluid flow 31.64 m³/h Pressure drop 48.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 143.77 not rated not rated not rated not rated not rated
40 238.75 143.66 not rated not rated not rated not rated
45 331.15 237.82 143.56 not rated not rated not rated
50 422.68 329.47 237.02 143.49 not rated not rated
55 513.80 420.28 328.04 236.41 143.56 not rated
60 604.71 510.72 418.25 326.93 236.07 143.78

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 110.88 not rated not rated not rated not rated not rated
40 182.48 110.78 not rated not rated not rated not rated
45 251.92 181.71 110.69 not rated not rated not rated
50 320.66 250.58 181.07 110.67 not rated not rated
55 389.08 318.77 249.45 180.61 110.73 not rated
60 457.32 386.65 317.18 248.60 180.37 110.93

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 238.748 41.40 78.4
Low speed (Y) 182.475 31.64 48.7

Dimensions

Dimension drawing of BE-380BD1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 3760 mm
F 1050 mm
G 4360 mm
E1 1130 mm
E2 1100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4360 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.