BE-391CC1-B04 C
369.32 kW
Defrost: None
Product code: BE-480CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 90,014 m³/h |
|---|---|
| External surface | 2,547.0 m² |
| Inner volume | 345.8 dm³ |
| Fin material | Aluminium |
| Net weight | 1,820 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 86.2 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-480CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 223.80 | not rated | not rated | not rated | not rated | not rated |
| 40 | 368.54 | 223.14 | not rated | not rated | not rated | not rated |
| 45 | 509.11 | 366.29 | 222.51 | not rated | not rated | not rated |
| 50 | 648.31 | 505.44 | 364.29 | 221.99 | not rated | not rated |
| 55 | 786.89 | 643.28 | 502.20 | 362.63 | 221.66 | not rated |
| 60 | 925.12 | 780.51 | 638.84 | 499.50 | 361.42 | 221.58 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 175.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 285.62 | 174.45 | not rated | not rated | not rated | not rated |
| 45 | 392.80 | 283.69 | 173.86 | not rated | not rated | not rated |
| 50 | 498.87 | 389.70 | 281.97 | 173.37 | not rated | not rated |
| 55 | 604.44 | 494.66 | 386.97 | 280.55 | 173.05 | not rated |
| 60 | 709.74 | 599.15 | 490.96 | 384.70 | 279.49 | 172.95 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 368.538 | 63.91 | 40.2 |
| Low speed (Y) | 285.624 | 49.53 | 25.5 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 10060 mm |
| F | 1050 mm |
| G | 10660 mm |
| E1 | 2430 mm |
| E2 | 2400 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 10660 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.