Skip to Content

Dry cooler BE-480FB1-B01 C

Dry cooler BE-480FB1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-480FB1-B01 C

Heat rejection i
365.45 kW
Air flow
89,900 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 89,900 m³/h
External surface 2,144.5 m²
Inner volume 391.6 dm³
Fin materialAluminium
Net weight 1,758 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 86.1 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-480FB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
365.453 kW Fluid flow 63.38 m³/h Pressure drop 70.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
283.026 kW Fluid flow 49.08 m³/h Pressure drop 44.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 222.63 not rated not rated not rated not rated not rated
40 365.45 221.81 not rated not rated not rated not rated
45 504.48 363.18 221.06 not rated not rated not rated
50 642.26 500.85 361.16 220.43 not rated not rated
55 779.45 637.31 497.65 359.48 220.02 not rated
60 916.33 773.22 632.96 494.98 358.23 219.87

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 173.94 not rated not rated not rated not rated not rated
40 283.03 173.20 not rated not rated not rated not rated
45 389.04 281.07 172.51 not rated not rated not rated
50 494.06 385.99 279.36 171.95 not rated not rated
55 598.61 489.94 383.31 277.93 171.56 not rated
60 702.91 593.45 486.33 381.08 276.87 171.41

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 365.453 63.38 70.0
Low speed (Y) 283.026 49.08 44.3

Dimensions

Dimension drawing of BE-480FB1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 10060 mm
F 1050 mm
G 10660 mm
E1 2430 mm
E2 2400 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 10660 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.